Evaluation unit air flow monitor NLSW45-6.1 SIL1 for environments up to 400°C, with SIL1 certification
Description
Description
✅ SIL1 hot gas flow monitor in accordance with IEC 61508/IEC 61511 for temperatures up to 400°C (monitoring up to 250°C is possible with the NLSW®45-6 SIL1 evaluation unit)
✅ Simple architecture: 1x F8/400°C SIL1 sensor, cost-effective high-temperature solution
✅ 1 changeover relay (250 V AC, 8 A, 2 kVA), dry contact
✅ High-temperature measurement range: 0.1 ... 20 m/s, medium temperature -20 to +400°C
✅ 4 stainless steel sensor designs: 50 ... 300 mm in length, V4A grade
✅ Compact IP40 housing (120×45×73 mm), DIN rail mounting
✅ Stepless setpoint adjustment, start-up delay 2 ... 60 s
✅ LED indicators for voltage and switching point; available in 24 V DC or 230 V AC
✅ Specifically designed for industrial furnaces, pelletizing/drying systems, thermal processing technology, heating coils, furnaces, cooling systems, and surface treatment
✅ Temperature gradient: max. 20 K/min
✅ Easy to maintain: Simple sensor cleaning, regular inspections
✅ German quality: CE and TÜV NORD certified, exida SIL1 certified
Evaluation unit air flow monitor NLSW45-6.1 SIL1 for environments up to 400°C, with SIL1 certification - 230 V AC is in stock and is sent as soon as it is available again
Delivery time: Available immediately
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
specification
specification
-
MediumGases
-
Device typeFlow evaluation unit for switch cabinet installation
-
Flow range0.1 ... 20 m/s
-
Medium temperature-20 ... 400°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP40
-
Special featuresStart-up delay, adjustable, approx. 2 ... 60 s, additional external start-up override
-
Output signalSwitching output
-
Switching output specification1 changer
-
Sensor break output signalRelay drops out
-
Sensor short-circuit output signalRelay drops out
-
Relay output specification1 changer
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
Housing dimensions120 mm x 45 mm x 73 mm
-
MountingDIN rail
-
Power supply24 V AC/DC, 230 V AC
-
Electrical connectionDIN rail
-
Max. power consumption3 VA
-
Recommended cable cross-section2.5 mm²
-
Current and contact rating250 VAC, 8 A, 2 kVA
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20 ... 50°C
-
CertificatesCE
-
ATEX certificationnone
-
SIL levelSIL1
-
Country of origin
-
Customs tariff number
-
HS code
Frequently Asked Questions
Was ist der Unterschied zwischen NLSW45-6.1 SIL1 und NLSW45-6.1 SIL2?
Was ist der Unterschied zwischen NLSW45-6.1 SIL1 und NLSW45-6.1 SIL2?
Welche F8/400°C-Sensoren sind verfügbar?
Welche F8/400°C-Sensoren sind verfügbar?
Warum ist der Messbereich bei 400°C reduziert?
Warum ist der Messbereich bei 400°C reduziert?
Für welche Anwendungen ist das Gerät geeignet?
Für welche Anwendungen ist das Gerät geeignet?
Warum ist Schaltschrankeinbau erforderlich?
Warum ist Schaltschrankeinbau erforderlich?
Welche Einbauhinweise sind bei 400°C zu beachten?
Welche Einbauhinweise sind bei 400°C zu beachten?
Ist eine Kabelverlängerung möglich?
Ist eine Kabelverlängerung möglich?
Wie wird das 400°C Gerät gewartet?
Wie wird das 400°C Gerät gewartet?