NLSW45-3 Ex Analog Evaluation Unit, Flow Monitoring for ATEX Areas with an Analog Output Signal (selectable between 4 ... 20 mA or 0 ... 10 V)
€632,42
Basic price
/
Unavailable
✅ Can be used in ATEX Zones 1 and 2 in conjunction with the 2 included Zener barriers
✅ Wide measurement range from 0.1 to 20 m/s with medium temperatures from 0°C to 60°C
✅ With analog output, 4 ... 20 mA, or alternatively 0 ... 10 V, suitable for control cabinet installation
✅ Designed for demanding industrial applications, IP40
✅ Example applications: Flow monitoring in paint shops, paper mills, and research facilities
⚠️ General note regarding the analog outputs:
Iout (-) must not be connected to the negative terminal of the supply voltage, nor to ground or earth.
The power supply to the downstream evaluation unit (e.g., PLC) must be galvanically isolated and must not establish a ground connection.
If necessary, a power isolator must be used.
Device type
Flow evaluation unit for switch cabinet installation
Flow range
0.1 ... 20 m/s
Medium temperature
0 ... 60°C
Relative pressure accuracy
Atmospheric pressure range
Atmospheric pressure accuracy
Differential pressure range
Differential pressure accuracy
Relative humidity accuracy
Number of differential pressure ranges
Maximum measuring range limit
Display
LED (voltage & switching point)
Switching point
Stepless adjustment (potentiometer)
Protection class evaluation unit
IP40
Special features
2 Zener barriers included in the scope of delivery Start-up override 5-60 sec., additional external start-up override
IK impact resistance rating
Color rendering index CRI
Max. differential pressure
product.metafields.custom.messgroesse1
Output signal
Analog output,
Switching output
Analog output specification
Switching output specification
1 changer
Digital output specification
Sensor break output signal
Relay drops out
Sensor short-circuit output signal
Relay drops out
Relay output specification
1 changer
Housing material
Polycarbonate glass fiber reinforced (UL94V-0)
Housing dimensions
120 mm x 45 mm x 73 mm
Mounting
DIN rail; to be mounted outside the ATEX zone
Fastening strap specification
Power supply
24 V DC ±5%,
24 V AC ±5%,
230 V AC ±5%
Electrical connection
Terminal strip
Max. power consumption
3 VA
Recommended cable cross-section
2.5 mm²
Current and contact rating
250 VAC,
8 A,
2 kVA
Minimum switching capacity
10 mA,
5 V DC
product.metafields.custom.leistung Bürde max.
Reverse polarity protection
Ambient temperature
-20 ... 50°C
ATEX certification
II 3G Ex ic IIC T4 Gc,
simple electrical equipment; Zone 1
Country of origin
Germany
Customs tariff number
90 26 80 20
Output signal accuracy LCD/Modbus
Signal output reproducibility
Switching function (flow)
Wet bulb temperature spec.
Dew point temperature spec.