Sensor F3 Ex SIL2 - Monitor and measure flows in ATEX zones, with SIL2 verification
Description
Description
✅ Sensor for flow monitoring of gases in potentially explosive atmospheres (ATEX) zones 1 and 2
✅ Classified according to Safety Integrity Level 2 (SIL2) - Corresponds to Performance Level d
✅ Measuring range 0.1 to 20.0 m/s
✅ Standard cable length 2.5 m - Optionally extendable up to 30 m
✅ For easy installation and alignment of the sensor in the air flow: Screw-in adapter with ATEX certification (available separately)
✅ Material: Nickel-plated brass (standard)alternatively available in stainless steel (V4A) or Teflon
✅ Special lengths on request available
✅ Depending on the desired output signal to be used with:
- Aevaluation unit NLSW®45-3 Ex SIL2 (for monitoring an adjustable switching point)
- Evaluation unit NLSW®45-3 Ex SIL2 Analog (for analog signal (4-20 mA or 0-10 V), as well as for monitoring an adjustable switching point)
Sensor F3 Ex SIL2 - Monitor and measure flows in ATEX zones, with SIL2 verification - 50 mm is in stock and is sent as soon as it is available again
Delivery time: Available immediately
Availability for collection could not be loaded
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
Bedienungsanleitung EN: Download
specification
specification
-
MediumGases
-
Device typeFlow sensor
-
Device designSensor
-
Flow range0.1 m/s ... 20 m/s
-
Medium temperature0°C ... 60°C
-
Protection class sensorIP67
-
Immersion depth50 mm, 130 mm, 165 mm, 300 mm, 400 mm, 500 mm, Special lengths on request
-
Process connectionPG7, optional G1/2-inch / G1/4-inch by means of reducer
-
Sensor materialMS58 nickel-plated, other materials on request (e.g. 1.4571)
-
Pressure resistance10 bar
-
Electrical connectionStandard cable length 2.5 m, Special lengths on request 3 x 0.5 mm²
-
Temperature gradient
-
CertificatesCE, Type-tested by TÜV Nord in accordance with DIN EN 61010-1 2011-07
-
ATEX certificationII 3G Ex ic IIC T4 Gc, simple electrical equipment; Zone 1
-
SIL levelSIL2
-
Customs tariff number
-
HS code
Häufig gestellte Fragen
Was ist die Besonderheit der dualen Zertifizierung mit Redundanz?
Was ist die Besonderheit der dualen Zertifizierung mit Redundanz?
Warum sind 2 Sensoren bei F3 Ex SIL2 erforderlich?
Warum sind 2 Sensoren bei F3 Ex SIL2 erforderlich?
Darf der F3 Ex SIL2 in Zone 1 eingesetzt werden?
Darf der F3 Ex SIL2 in Zone 1 eingesetzt werden?
Was bedeutet "Performance Level d"?
Was bedeutet "Performance Level d"?
Wie müssen die beiden Sensoren positioniert werden?
Wie müssen die beiden Sensoren positioniert werden?
Welche Eintauchtiefen sind verfügbar?
Welche Eintauchtiefen sind verfügbar?
Mit welcher Auswerteeinheit wird F3 Ex SIL2 betrieben?
Mit welcher Auswerteeinheit wird F3 Ex SIL2 betrieben?
Was geschieht bei Sensorausfall?
Was geschieht bei Sensorausfall?