NLSW45-3 air flow monitor evaluation unit with SIL1 certification
Description
Description
✅ SIL1 airflow monitor in accordance with IEC 61508/IEC 61511 (Performance Level c)
✅ Simple architecture: 1 F3 SIL1 sensor, cost-effective SIL solution
✅ 1 changeover relay (250 V AC, 8 A, 2 kVA), dry contact
✅ Extended measurement range: 0.1–30 m/s; medium temperature: -25 to +120°C
✅ 6 sensor configurations: 50–500 mm in length, easy installation
✅ Compact IP40 housing (120×45×73 mm), DIN rail mounting
✅ Continuously adjustable setpoint, start-up delay 5–60 s (jumper)
✅ LED indicators for voltage and setpoint, 24 V/230 V available
✅ Control cabinet installation required (IP20 terminals), easy installation
✅ Applications: heating coils, fans, dampers, motor cooling, DDC
✅ Optional: ATEX version for Zones 1/2 available with 2 Zener barriers
✅ Easy to maintain: Simple sensor cleaning with lukewarm soapy water
✅ German quality: CE and TÜV NORD certified, exida SIL1 certified
NLSW45-3 air flow monitor evaluation unit with SIL1 certification - 1 x 230 V AC is in stock and is sent as soon as it is available again
Delivery time: Available immediately
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
Bedienungsanleitung EN: Download
specification
specification
-
MediumGases
-
Device typeFlow evaluation unit for switch cabinet installation
-
Flow range0.1 ... 30 m/s
-
Medium temperature-25 ... 120°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP40
-
Special featuresStart-up override 5-60 sec., additional external start-up override
-
Output signalSwitching output
-
Switching output specification1 changer
-
Sensor break output signalRelay drops out
-
Sensor short-circuit output signalRelay drops out
-
Relay output specification1 changer
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
MountingDIN rail
-
Power supply24 V AC/DC ±5%, 230 V AC ±5%
-
Electrical connectionTerminal strip
-
Max. power consumption3 VA
-
Recommended cable cross-section2.5 mm²
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20 ... 50°C
-
CertificatesCE, Type-tested by TÜV Nord in accordance with DIN EN 61010-1 2011-07
-
ATEX certificationnone
-
SIL levelSIL1
-
Country of origin
-
Customs tariff number
-
HS code
Frequently Asked Questions
Was ist der Unterschied zwischen SIL1 und SIL2 beim NLSW45-3?
Was ist der Unterschied zwischen SIL1 und SIL2 beim NLSW45-3?
Welche Sensorbauformen sind verfügbar?
Welche Sensorbauformen sind verfügbar?
Wie funktioniert die Anlaufüberbrückung?
Wie funktioniert die Anlaufüberbrückung?
Warum muss das Gerät im Schaltschrank montiert werden?
Warum muss das Gerät im Schaltschrank montiert werden?
Ist eine ATEX-Version verfügbar?
Ist eine ATEX-Version verfügbar?
Welche Einbauhinweise sind zu beachten?
Welche Einbauhinweise sind zu beachten?
Was passiert bei Sensorausfall?
Was passiert bei Sensorausfall?
Wie wird das Gerät gewartet?
Wie wird das Gerät gewartet?