Evaluation unit NLSW45-3 SIL2, flow monitoring with SIL2 certification
Description
Description
✅ SIL2-certified redundant flow monitor in accordance with IEC 61508-5:2010 for safety-critical applications
✅ 2-channel system with separate F6.x SIL2 sensors and integrated evaluation units for maximum operational safety
✅ Calorimetric measurement principle: water 0.05–3 m/s, air 0.5–20 m/s with automatic temperature compensation
✅ Robust relay switching outputs, 250 V AC/8 A per channel, for direct connection to a PLC or safety PLC
✅ Integrated sensor monitoring: Automatic short-circuit and open-circuit detection with relay deactivation
✅ Flexible power supply: 24 V AC/DC or 230 V AC for universal integration
✅ Precision potentiometers for independent setpoint adjustment of both channels with LED status indicators
✅ Media temperature: -15 to 80°C; ambient temperature: -20 to 50°C for harsh industrial environments
✅ Compact DIN rail mounting, with optional adapter, for control cabinet installation
✅ TÜV NORD certified according to DIN EN 61010-1:2011-07 – Made in Germany: Safety and Precision
✅ Main applications: Chemical, pharmaceutical, power plants, oil/gas, water treatment, automotive industry
✅ Maintenance-free operation without moving parts; sensor cable up to 50 m long
Evaluation unit NLSW45-3 SIL2, flow monitoring with SIL2 certification - 230 V AC is in stock and is sent as soon as it is available again
Delivery time: Available immediately
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
Bedienungsanleitung EN: Download
specification
specification
-
MediumLiquids, Gases
-
Device typeFlow evaluation unit for switch cabinet installation, or installation at the measuring point
-
Flow range0.1 ... 30 m/s
-
Medium temperature-15 … 80°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP67
-
Special features2 sensors required (SIL2)
-
Output signalSwitching output
-
Switching output specification2 changeover contacts (1 per channel)
-
Sensor break output signalRelay drops out
-
Sensor short-circuit output signalRelay drops out
-
Relay output specification2 changeover contacts (1 per channel)
-
Housing materialPolyamide (UL94V-0)
-
Housing dimensions85 mm x 165 mm x 55 mm
-
MountingMounting kit included, Mounting on DIN rail optional
-
Power supply24 V AC/DC ±10%, 230 V AC ±10%
-
Electrical connectionTerminal strip
-
Max. power consumption5 VA (24 V), 10 VA (230 V)
-
Recommended cable cross-section2.5 mm²
-
Current and contact rating250 VAC, 8 A, 2 kVA
-
Minimum switching capacity10 mA / 5 V DC
-
Ambient temperature-20 ... 50°C
-
CertificatesCE, Type-tested by TÜV Nord in accordance with DIN EN 61010-1 2011-07
-
ATEX certificationnone
-
SIL levelSIL2
-
Country of origin
-
Customs tariff number
-
HS code
Frequently Asked Questions
Was bedeutet SIL2-Zertifizierung beim NLSW45-4 und wie unterscheidet er sich vom Standard NLSW45-4?
Was bedeutet SIL2-Zertifizierung beim NLSW45-4 und wie unterscheidet er sich vom Standard NLSW45-4?
Welche F6.x SIL2 Sensoren sind für den NLSW45-4 SIL2 verfügbar?
Welche F6.x SIL2 Sensoren sind für den NLSW45-4 SIL2 verfügbar?
Welche Medien-Beschränkungen gelten beim NLSW45-4 SIL2?
Welche Medien-Beschränkungen gelten beim NLSW45-4 SIL2?
Welche Wartungsintervalle sind für SIL2-konforme Nutzung erforderlich?
Welche Wartungsintervalle sind für SIL2-konforme Nutzung erforderlich?
Für welche Industriezweige ist der NLSW45-4 SIL2 hauptsächlich konzipiert?
Für welche Industriezweige ist der NLSW45-4 SIL2 hauptsächlich konzipiert?
Wie erfolgt die korrekte Montage der redundanten Sensoren?
Wie erfolgt die korrekte Montage der redundanten Sensoren?
Wie erfolgt die Schaltpunkt-Einstellung beim NLSW45-4 SIL2?
Wie erfolgt die Schaltpunkt-Einstellung beim NLSW45-4 SIL2?
Welche Spannungsversorgungen stehen für den NLSW45-4 SIL2 zur Verfügung?
Welche Spannungsversorgungen stehen für den NLSW45-4 SIL2 zur Verfügung?