Flow monitor RLSW6AR (incl. sensor, automatic reset) with 2 relay outputs for HVAC applications
Description
Description
✅ RLSW6AR Dual-Relay Airflow Monitor with F9 sensor (100 m cable max.) and automatic reset for maintenance-free HVAC monitoring, 0.1–25 m/s
✅ Intelligent dual-relay system: Flow relay (2 kVA) + alarm relay (2.5 kVA), each with SPDT changeover contacts rated at 250 V AC/8 A
✅ **Automatic Reset Function:** Faults are NOT logged—automatic recovery upon return of airflow, unlike the RLSW6 with fault memory (optional upon request)
✅ Compliant with DIN 57100 Part 420 for heating coil safety: prevents harmful heating/humidification without air exhaust in critical applications
✅ Precise timing control: 15–120 s power-on delay (fan ramp-up) + 2–20 s power-off delay (false alarm prevention) via potentiometer
✅ Modular F9 sensor design: separate airflow sensor with a 1.5 mm² extension cable up to 100 m, installation orientation-independent, IP67 protection rating
✅ Dual power supply: 24 V AC/DC or 230 V AC for flexible integration in control cabinets without external power supplies
✅ Triple-LED status system: Green = Operating, Red = Flow > threshold value, Yellow = Alarm in case of flow loss or startup failure
✅ 11-terminal connection (2.5 mm²) for complex dual-relay wiring with separate flow and alarm outputs
✅ Rugged 55×165×85 mm IP65 housing for control cabinet installation; F9 sensor with optional plastic flange (Part No. 79781/14)
✅ HVAC specialization: control dampers, air curtain systems, DDC systems, exhaust systems, supply air systems, machinery and plant engineering
✅ CE-compliant for European installation; maintenance-free calorimetric technology with no moving parts, unlike mechanical paddle systems
Flow monitor RLSW6AR (incl. sensor, automatic reset) with 2 relay outputs for HVAC applications - 230 V AC is in stock and is sent as soon as it is available again
Delivery time: Available immediately
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
Bedienungsanleitung EN: Download
specification
specification
-
MediumGases
-
Device typeCompact flow device
-
Device designCompact device including sensor (remote)
-
DisplayYellow LED at flow velocities > switching point, green LED during operation
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP65
-
Protection class sensorIP67
-
Special featuresAlarm with automatic reset or manual acknowledgement Adjustable start-up delay 0 ... 60 s 2 relay outputs
-
Output signalSwitching output
-
Switching output specification2 relay outputs (changeover contact) Relay picks up on flow
-
Sensor break output signalRelay drops out
-
Sensor short-circuit output signalRelay drops out
-
Relay output specification2 relay outputs (changeover contact) Relay picks up on flow
-
Immersion depth165 mm, Custom lengths available upon request
-
Housing materialPolyamide, UL94-V0
-
Sensor materialMS58, nickel-plated (optionally available in stainless steel)
-
Pressure resistance10 bar
-
Housing dimensions55 mm x 165 mm x 85 mm
-
Power supply24 V AC/DC ±5%, 230 V AC ±5%
-
Electrical connection11 terminals (2.5 mm²)
-
Max. power consumption5 VA
-
Current and contact rating250 VAC, 8 A, 2 kVA
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20 ... 60°C
-
Optimal inlet path>5 DN
-
Optimal outlet path>3 DN
-
Temperature gradient
-
CertificatesCE
-
ATEX certificationnone
-
SIL levelnone
-
Country of origin
-
Customs tariff number
-
HS code
-
Pollution degree
Frequently Asked Questions
Was unterscheidet den RLSW6AR vom RLSW6 und warum sollte ich die AR-Variante wählen?
Was unterscheidet den RLSW6AR vom RLSW6 und warum sollte ich die AR-Variante wählen?
Wie funktioniert das Dual-Relais-System beim RLSW6AR und welche Schaltlogik gilt?
Wie funktioniert das Dual-Relais-System beim RLSW6AR und welche Schaltlogik gilt?
Was ist das F9-Sensor-System und welche Installation-Vorteile bietet es?
Was ist das F9-Sensor-System und welche Installation-Vorteile bietet es?
Welche Zeitfunktionen bietet der RLSW6AR und wie stelle ich sie optimal ein?
Welche Zeitfunktionen bietet der RLSW6AR und wie stelle ich sie optimal ein?
Für welche DIN57100-konformen Anwendungen ist der RLSW6AR besonders geeignet?
Für welche DIN57100-konformen Anwendungen ist der RLSW6AR besonders geeignet?
Welche Schaltleistung bieten die beiden Relais beim RLSW6AR?
Welche Schaltleistung bieten die beiden Relais beim RLSW6AR?
In welchen Industriebereichen wird der RLSW6AR typischerweise eingesetzt?
In welchen Industriebereichen wird der RLSW6AR typischerweise eingesetzt?
Welche Installation-Besonderheiten muss ich beim RLSW6AR beachten?
Welche Installation-Besonderheiten muss ich beim RLSW6AR beachten?