ATEX junction boxes Series 8118
Description
Description
✅ Explosion-proof junction box for Ex zones 1, 2, 21 and 22
✅ Made of glass fiber reinforced polyester resin, extremely robust, halogen-free and silicone-free
✅ 4, 5 or 8 Sheath terminalsdepending on size
✅ Clamping range: 1.5 mm² up to 10 mm²
✅ Operating voltage: up to 750 V AC depending on variant
✅ Dimensions, depending on variant: 85x85, 115x115, 145x145 mm
✅ Ship approval: DNV
✅ Certified for - Ex e applications:
II 2 G Ex eb IIC T6 / T5 Gb
II 2 D Ex tb IIIC T80 °C / T95 °C Db
Voltage - to 750 V Operating voltage, max. operating current -
depending on cable cross-section and loaded terminals 50 A
✅ Certified for - Ex e applications Junction box with fuses (optional)
II 2 G Ex e mb IIC T6 / T4 Gb
II 2 D Ex tb IIIC T80 °C / T130 °C Db
Voltage - to 250 V Operating voltage, max. operating current -
depending on cable cross-section and loaded terminals 25 A
✅ Certified for - Ex e applications
II 2 G Ex eb IIC T6 / T5 Gb
II 2 D Ex tb IIIC T80 °C / T95 °C Db
Voltage - up to 550 V Operating voltage, max. operating current -
depending on cable cross-section and loaded terminals 25 A
✅ Certified for - Ex i applications
II 2 G Ex ia ib IIC T6 Gb
II 2 D Ex tb IIIC T80 °C Db
Voltage selection - Up to 60 V Operating voltage, max. operating current -
depending on cable cross-section and loaded terminals 35 A
ATEX junction boxes Series 8118 - Ex e (750 V) / -40 ... 40°C (T6); -40 ... 55°C (T5) / 4x M25x1.5 (7-17) / 5 St 6 mm² is in stock and is sent as soon as it is available again

Availability for collection could not be loaded
specification
specification
-
Device typeAtex junction boxes
-
Device designCompact
-
Protection class housingIP66
-
Housing dimensions85 x 85 x 55 mm, 115 x 115 x 64 mm, 145 x 145 x 71 mm
-
Electrical connectionM20x1.5 cable gland, M25x1.5 cable gland, M32x1.5 cable gland, M20x1.5 sealing plug, M25x1.5 sealing plug, M32x1.5 sealing plug, without hole, according to order
-
Recommended cable cross-section2.5 mm², 4 mm², 6 mm², 10 mm²
-
Current and contact rating16 A, 20 A, 25 A, 35 A, 50 A
-
Ambient temperature40 °C ... +40 °C (T6) -40 °C ... +55 °C (T5), -40 °C ... +75 °C (T6), -60 °C ... +40 °C (T6) -60 °C ... +55 °C (T5), -20 °C ... +75 °C (T6)
-
ATEX certificationII 2 G Ex eb IIC T6 / T5 Gb, II 2 G Ex e mb IIC T6 / T4 Gb, II 2 G Ex ia ib IIC T6 Gb, II 2 D Ex tb IIIC T80 °C / T95 °C Db, II 2 D Ex tb IIIC T80 °C Db, II 2 D Ex tb IIIC T80 °C / T130 °C Db