FlowGuard® FS400 - Flow monitoring of liquid media with analog (4 ... 20 mA) and/or switching output
Description
Description
✅ Flow monitor for liquid media in the range of 4 ... 400 cm/s with relay or analog (4 ... 20 mA) and status output (PNP or NPN) for monitoring a flow threshold
✅ Ten LEDs indicate flow rate and contact closure
✅ Equipped with 2 control buttons for setting the switching point
✅ Available with 65 mm, 125 mm and 175 mm immersion depth
✅ Robust design for industrial environments, IP67
✅ Process connection: according to DIN2353, suitable for G1/2-inch or G1/4-inch adapters (not included in the scope of delivery), adapters for NPT1/4-inch, M14x1.5, terminal DN25 and terminal DN50 also available on request)
✅ Areas of application: Water industry, agriculture, biogas plants, food industry, power plants and many more.
✅ Alternatively also available as DNV version, in stainless steel to DIN 1.4410
FlowGuard® FS400 - Flow monitoring of liquid media with analog (4 ... 20 mA) and/or switching output - 65 mm / 1x active contact PNP + analog output 4 ... 20 mA / none is in stock and is sent as soon as it is available again
Delivery time: Selected variants available immediately
Availability for collection could not be loaded
specification
specification
-
MediumLiquids
-
Device typeCompact flow device
-
Device designCompact device including sensor (permanently mounted)
-
Flow range0.04 m/s ... 4 m/s
-
Flow accuracy±0.02 ... 0.08 m/s
-
Medium temperature0 ... 80°C
-
Display10 three-color LEDs for flow velocity, 1 LED for temperature
-
Switching pointStepless adjustment via 2 buttons
-
Protection class evaluation unitIP67
-
Protection class sensorIP67
-
Special featuresEmpty pipe detection is displayed as 0 flow, Calorimetric measuring principle, Optional relay output for media temperature, optional 2 real relay outputs for flow bandwidth
-
Output signalAnalog output, Switching output, Temperature switching point
-
Switching output specificationSwitching output active PNP/ NPN; switches on flow, Switching output passive (relay); switches on flow
-
Relay output specificationSwitching output active PNP/ NPN; switches on flow, Switching output passive (relay); switches on flow
-
Immersion depth65, 125, 175, Special lengths on request
-
Process connectionG1/2-inch
-
Housing materialStainless steel 1.4404, Stainless steel 1.4410; DNV version
-
Sensor materialStainless steel 1.4404, Stainless steel 1.4410; DNV version
-
Pressure resistance63 bar
-
Weight
-
Housing dimensions91 mm x 74 mm x 60 mm
-
Dimensions91 mm x 74 mm x 60 mm
-
Power supply24 V DC ±10%
-
Electrical connectionM12 x 1 / 4 pin connector
-
Max. power consumption1.5 ... 4 VA
-
Current and contact rating60 V, 130 mA, 500 mW, SSR, passive, potential-free, max. 350 V AC/DC, 150 mA, 400 mW
-
Ambient temperature-10 ... 55°C
-
Optimal inlet path>5 DN
-
Optimal outlet path>3 DN
-
CertificatesCE
-
ATEX certificationNone
-
SIL levelnone
-
Country of origin
-
Customs tariff number
-
HS code
Häufig gestellte Fragen
Was ist das kalorimetrische Messprinzip und welche Vorteile bietet es?
Was ist das kalorimetrische Messprinzip und welche Vorteile bietet es?
Für welche Medien ist der FlowGuard® FS400 geeignet?
Für welche Medien ist der FlowGuard® FS400 geeignet?
Welche Varianten des FS400 sind verfügbar und worin unterscheiden sie sich?
Welche Varianten des FS400 sind verfügbar und worin unterscheiden sie sich?
Wie wird der Schaltpunkt eingestellt?
Wie wird der Schaltpunkt eingestellt?
Gibt es spezielle Schutzarten oder Zulassungen für sensible Bereiche?
Gibt es spezielle Schutzarten oder Zulassungen für sensible Bereiche?
Müssen bestimmte Einbaubedingungen berücksichtigt werden?
Müssen bestimmte Einbaubedingungen berücksichtigt werden?
Ist eine Temperaturüberwachung möglich?
Ist eine Temperaturüberwachung möglich?
Wo wird das Gerät typischerweise eingesetzt?
Wo wird das Gerät typischerweise eingesetzt?