Evaluation unit NLSW45-3 SIL2 Analog, flow monitoring with SIL2 certification and analog output (4-20 mA)
Description
Description
✅ Flow monitoring with SIL2 certification according to IEC 62061 (corresponds to performance level d according to EN ISO 13849-1)
✅ Wide measuring range from 0.1 to 35 m/s with media temperatures from 0°C to 60°C
✅ With switching output suitable for switch cabinet installation
✅ Developed for demanding industrial applications, IP40
✅ Redundant design of the evaluation electronics and use of 2 sensors required
Evaluation unit NLSW45-3 SIL2 Analog, flow monitoring with SIL2 certification and analog output (4-20 mA) - 230 V AC is in stock and is sent as soon as it is available again

Availability for collection could not be loaded
Technische Zeichnung 3D: Download
Technische Zeichnung 2D: Download
Bedienungsanleitung DE: Download
Bedienungsanleitung EN: Download
specification
specification
-
MediumGases
-
Device typeFlow evaluation unit for switch cabinet installation, Installation at the measuring point
-
Flow range0,1 ... 30 m/s
-
Medium temperature0 ... 85°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer), Independent of the analog measuring range
-
Protection class evaluation unitIP65
-
Special features2 sensors required (SIL2)
-
Output signalSwitching output, Analog output
-
Switching output specification2 changeover contacts (per channel)
-
Sensor break output signalRelay drops out
-
Sensor short-circuit output signalRelay drops out
-
Relay output specification2 changeover contacts (per channel)
-
Housing materialPolyamide (UL94V-0)
-
Weight
-
Housing dimensions85 mm x 165 mm x 55 mm
-
MountingMounting kit included, Mounting on DIN rail optional
-
Power supply24 V AC/DC ±10%, 230 V AC ±10%
-
Electrical connectionTerminal strip
-
Max. power consumption5 VA
-
Recommended cable cross-section2.5 mm²
-
Current and contact rating250 V AC, 4 A, 1 kVA / 150W
-
Minimum switching capacity100 mA/ 5 V DC
-
Ambient temperature-20 ... 60°C
-
CertificatesCE
-
ATEX certificationnone
-
SIL levelSIL2
-
Country of origin
-
Customs tariff number
-
HS code
Häufig gestellte Fragen
Was bedeutet "redundant" beim NLSW45-3 SIL2 Analog?
Was bedeutet "redundant" beim NLSW45-3 SIL2 Analog?
Können beide Analogausgänge (4–20mA und 0–10V) gleichzeitig genutzt werden?
Können beide Analogausgänge (4–20mA und 0–10V) gleichzeitig genutzt werden?
Welche Sensorbauformen stehen zur Verfügung?
Welche Sensorbauformen stehen zur Verfügung?
Wie werden die beiden Sensoren im Rohr positioniert?
Wie werden die beiden Sensoren im Rohr positioniert?
Ist eine ATEX-Version verfügbar?
Ist eine ATEX-Version verfügbar?
Welche Wartungsintervalle gelten für SIL2-Anwendungen?
Welche Wartungsintervalle gelten für SIL2-Anwendungen?
Was passiert bei Sensorfehler oder -ausfall?
Was passiert bei Sensorfehler oder -ausfall?